DIN Rail Power Supplies
Industrial Power Supplies Compact DIN Rail Power Supply
Available in 24 and 48vDC models, Perle Industrial-grade Power Supplies are reliable sources of power designed stand up to harsh industrial environments.
- Adheres to a variety of industry-recognized standards to ensure the highest level of durability and adaptability under harsh environmental conditions
- Compact size with standard DIN-Rail attachment
- Universal input range
- Short circuit , overload and over voltage protection
- LED indicator for power

Perle Industrial-grade Power Supplies are designed to stand up to extreme temperatures, surges, vibrations, and shocks found in industrial automation, government, military, oil and gas, mining and outdoor applications.
IDPS 24v and 48vDC power supplies are hardened to provide superior reliability in extended operating temperatures from -20 to 70C.
These power supplies are ideal for providing reliable power to:
IDPS-24-40-XT | IDPS-48-240-XT | UNO-PS/1AC/24DC/150W | TRIO-PS/1AC/48DC/10 | |
---|---|---|---|---|
Output | ||||
Nominal DC Voltage | 24 V | 48 V | 24 V | 48 V |
Max Current | 1.7 A | 5 A | 6.25 A | 10 A |
Rated Power | 40.8 watts | 240 watts | 150 watts | 480 watts |
Ripple and Noise | 150 mV p-p | < 40 mVpp | < 50 mVpp | |
Adjustable Voltage Range | 24 – 30 V | 48 – 53 V | 24 – 28 V | 30 to 56 V DC |
Load De-rating | De-rating from 60C 60% of full load at 70C |
De-rating from 40C 0% of full load at 70C |
55 °C … 70 °C (2.5%/K) | 55 °C … 70 °C (2.5%/K) |
Output Connectors | 4-pin terminal block ( V+,V-,V+,V- ) | |||
Input | ||||
Input Voltage Range | 85 – 264VAC 120 – 370VDC |
85 – 264VAC | ||
Frequency Range | 47 – 63Hz | 45 Hz – 65 Hz | ||
Efficiency ( Typical ) | 88% | 85% | >94% | >91% |
AC Current ( Typical ) | 1.1A/115VAC 0.7A/230VAC |
2.8A/115VAC 1.4A/230VAC |
1.4 A/120 VAC 0.8 A/230 VA |
4.6 A/120 VAC 2.4 A/230 VAC |
Inrush Current ( Typical ) | 30A/115VAC 60A/230VAC |
27A/115VAC 45A/230VAC |
< 50A ( typical ) | < 15A |
Input Connectors | 3-pin terminal block | |||
Protection | ||||
Over Voltage | 31.2 – 36V | 54 – 60V | – | limited to approx. 60 V DC |
Environmental Specifications | ||||
Operating Temperature Ranges | -20 to 70C ( -4 to 158F ) |
-10 to 70C ( 14 to 158F ) |
-25 °C to 70 °C (-13 to 158F ) |
|
Storage Temperature Range | -40 to 85C ( -40 to 185F ) |
-20 to 85C ( -4 to 185F ) |
-40 to 85C ( -40 to 185F ) |
|
Operating Humidity Range | 20 – 90% RH non-condensing | ≤ 95 % (at 25 °C, non-condensing) | 95 % (at 25 °C, non-condensing) | |
Din Rail Mountable | Mounts to standard 35 mm DIN rail in accordance with DIN EN 60175 | Mounts to standard 35 mm DIN rail in accordance with DIN EN 60175 | ||
MTBF | 301,700 hours based on MIL-HDBK-217F @ 25C |
289,900 hours based on MIL-HDBK-217F @ 25C |
> 868000 h (40°C) (IEC 61709, SN 29500) |
> 500 000 h in acc. with IEC 61709 (SN 29500) |
Product Weight and Dimensions | ||||
Weight | 0.26kg 0.57lbs |
1.12kg 2.5lbs |
0.5 kg 1.1lbs |
1.9 kg 4.2lbs |
Dimensions | 40 x 90 x 100mm, 1.57 x 3.54 x 3.94 inches |
125.5 x 125.2 x 100mm 4.94 x 4.93 x 3.94 inches |
37 x 130 x 125mm | 115 x 130 x 152.5mm |
Packaging | ||||
Shipping Weight | 0.29kg 0.64lbs |
1.23kg 2.7lbs |
0.6 Kg 1.3lbs |
2.09 Kg 4.6lbs |
Shipping Dimensions | 45 x 105 x 110mm 1.8 x 4.1, 4.3 inches |
145 x 145 x 125mm 5.7 x 5.7x 4.9 inches |
200 x 300 x 70 mm 7.9 x 11.8 x 2.8 inches |
200 x 230 x 150 mm 7.9 x 9.0 x 5.9 inches |
Standards and Certifications | ||||
Safety | UL508, UL60950-1, TUV EN60950-1 | EN 60950-1/VDE 0805 (SELV) | EN 60950-1/VDE 0805 (SELV) | |
Emissions | EN55011, EN55022 (CISPR22) | EN55011, EN55022 (CISPR22) | ||
EN61204-3 , Class B EN61000-3-2,-3 | EN61204-3 , Class B EN61000-3-2,-3 | |||
Mechanical Stability | Vibration: IEC 60068-2-6 | Vibration: IEC 60068-2-6 | ||
EMC and Immunity | EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A | EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A | Conformance with EMC Directive 2014/30/EU EN 61000-6-2:2005 | |
Industrial Safety | UL508 (Safety standard for Industrial Control Equipment ) | |||
Class I, Div. 2 Group A, B, C, D HazardousLocations T4 approved | – | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) | – | |
Rail applications | – | – | – | EN 50121-4 |
Environmental | Reach, RoHS and WEEE Compliant | Reach and RoHS Compliant | ||
Other | EAR99 | EAR99 | ||
HTSUS Number: 8517.62.0050 | HSTUS Number: 8504.40.30 | |||
2 year warranty | 1 year warranty |
Documentation
Downloads:Manuals |
Description | Power Cord | Product Part Number | |
---|---|---|---|
![]() |
IDPS-24-40-XT – DIN-Rail 24 VDC, 40Watt power supply with universal 85 to 264 VAC or 120-370 VDC input , -20 to 70°C extended operating temperature. | None | |
![]() |
IDPS-48-240-XT – DIN-Rail 48 VDC, 240Watt power supply with universal 85 to 264 VAC or 120-370 VDC input , -10 to 70°C extended operating temperature. | None | 07012040 |
![]() |
UNO-PS/1AC/24DC/150W Power Supply – DIN-Rail 24 VDC , 150 Watt power supply with universal 85 to 264 VAC, -25 to 70°C extended operating temperature | N /A | |
![]() |
TRIO-PS/1AC/48DC/10 Power Supply – DIN-Rail 48 VDC , 480 Watt power supply with universal 85 to 264 VAC, 30 to 56V DC output range adjustable, -25 to 70°C extended operating temperature | N /A |